Basis for the provision of isolation valves on pipelines carrying combustible gases, liquefied hydrocarbons, and combustible liquids entering or leaving a process unit

Oct 20, 2026

GB 50160-2008 (2018 Edition) "Code for Fire Protection Design of Petrochemical Enterprises"

7.2.16 For pipelines transporting combustible gases, liquefied hydrocarbons, or combustible liquids into or out of a process unit, isolation valves and spectacle blinds (figure-eight blinds) shall be installed at the unit boundary. A platform shall be provided at the location of the isolation valves; for platforms with a length of 8 meters or greater, ladders shall be provided at both ends.

SH/T 3012-2011 "Specification for Layout Design of Metal Piping in Petrochemical Plants"

3.1.20 For pipelines transporting combustible gases, liquefied hydrocarbons, or combustible liquids into or out of a process unit, isolation valves and blinds shall be installed at the unit boundary. A platform shall be provided at the location of the isolation valves; for platforms with a length of 8 meters or greater, ladders shall be provided at both ends.

GB 51283-2020 "Code for Fire Protection Design of Fine Chemical Enterprises"

7.2.2 For pipelines transporting combustible gases, liquefied hydrocarbons, or combustible liquids into or out of a production facility, isolation valves and spectacle blinds (figure-eight blinds) shall be installed at the facility boundary. A platform shall be provided at the location of the isolation valves.

GB/T 20801.1-2025 "Pressure Piping Code - Part 1: Industrial Piping"

G.2 j) For pipelines transporting flammable media into or out of a process unit, isolation valves and spectacle blinds (figure-eight blinds) shall be installed at the unit boundary. A platform shall be provided at the location of the isolation valves; for platforms with a length of 8 meters or greater, ladders shall be provided at both ends.