| On-Site Safety Inspection Checklist for Diesel Storage | ||||
| No. | Inspection Item | Inspection Standard | Inspection Result | Issue Description |
| I. Overall Environment of the Tank Farm and Impermeable Containment Dikes | ||||
| 1 | Fire-containment Bund | Bund height: 21.2m; intact with no cracks, holes, or seepage; capacity exceeds that of the largest tank; free of debris, accumulated water, or oil. | ||
| 2 | Anti-seepage Treatment | Bund floor and inner wall anti-seepage layers are intact, with no damage or surface crumbling; no exposed soil within the bund. | ||
| 3 | Drainage Switching Valve | Oil-water switching valve installed at the rainwater collection sump; closed during normal operation (oil retention mode); clearly labeled; valve is in good condition with no leakage. | ||
| 4 | Tank Farm Access | Fire access routes and inspection paths are unobstructed, free from vehicles or debris; road surfaces are paved and in good condition. | ||
| 5 | Open Flame Control | Smoking and hot work strictly prohibited in the area; fire safety signage is clearly visible; no unauthorized ignition sources or heating equipment. | ||
| 6 | Separation Distances | Fire separation distances between storage tanks and buildings, open flame sources, or power distribution rooms comply with GB50016 and GB50160 standards. | ||
| II. Structural Safety of the Storage Tank Body | ||||
| 7 | Tank Shell | Shell and heads show no deformation, bulging, severe corrosion, or leakage; welds show no cracking or oil seepage. | ||
| 8 | Anti-corrosion Coating | External anti-corrosion coating is intact, with no large-scale peeling or rusting; rust removal and touch-up painting are performed promptly. | ||
| 9 | Bottom Plate | No signs of leakage; no oil stains at the base of the perimeter wall; complete records of periodic thickness measurements. | ||
| 10 | Manholes and Clean-out Ports | Cover plate seals are in good condition; bolts are complete and tightened; gaskets show no signs of aging or oil leakage. | ||
| 11 | Foundation and Supports | Tank supports and concrete foundations show no cracking, settlement, or tilting; anti-corrosion coating is in good condition. | ||
| 12 | Level Gauge Connections | No leakage at pipe flanges; gaskets are intact; no diesel leakage. | ||
| III. Liquid level, temperature, and pressure monitoring facilities | ||||
| 13 | Local Level Gauge | Glass tube/magnetic flap level gauges are clear, free of blockages and leaks; "Low-Low" level red-line markings are intact. | ||
| 14 | Remote Level System | DCS and field level readings match; "Low" level alarms and "Low-Low" level interlocks are functioning correctly. | ||
| 15 | Level Control | Storage tank fill level ≤59% of rated capacity; overfilling is strictly prohibited; no records of exceeding level limits. | ||
| 16 | Thermometer | Temperature measuring device is in good condition, readings are accurate, and there is no damage or leakage. | ||
| 17 | Breather Valve/Flame Arrester | Breather valve operates smoothly without jamming, icing, or fouling; flame arrester is in good condition and free of blockages; periodic cleaning records are maintained. | ||
| 18 | Pressure Gauge | The pressure gauge is within its calibration validity period; the dial is clear, and there are no leaks. | ||
| IV. Fire Protection and Emergency Facilities | ||||
| 19 | Fire Extinguishing Materials | Dry powder fire extinguishers: sufficient quantity, normal pressure, within validity period; securely mounted yet easily accessible | ||
| 20 | Foam Fire Extinguishing System (Large Storage Tanks) | Foam concentrate within validity period; piping free of leaks; valves clearly labeled; records of periodic pressure testing and drills available | ||
| 21 | Fire Cooling Water System | Fire pumps and sprinkler piping in good condition; valves operate smoothly; adequate water supply | ||
| 22 | Fire-extinguishing Sand & Oil-absorbent Mats | Dedicated fire sand pit dry and well-stocked; oil-absorbent mats and pads properly positioned | ||
| 2 | Emergency Supplies | Spill containment booms, cleanup tools, protective gloves, and gas masks complete and in good condition | ||
| 24 | Emergency Lighting & Warning Lights | Emergency lighting functional; explosion-proof warning lights in good condition | ||
| 25 | Fire Access Routes & Fire Hydrants | Fire hydrant water pressure normal; accessories complete; no obstructions | ||
| V. Anti-static, Lightning Protection, and Explosion Protection Systems | ||||
| 26 | **Grounding** | Storage tank bodies, piping, and metal components of bund walls are properly grounded; grounding resistance is tested annually (limit: ≤10Ω). | ||
| 27 | **Static Bonding** | Metal bonding connections between pipe flanges and valves are intact and unbroken; anti-static bonding for loading/unloading hoses is correctly connected. | ||
| 28 | **Explosion-proof Electrical Equipment** | Lighting, motors, junction boxes, and switches in the hazardous area are of the Ex explosion-proof type; no damage or loss of explosion-proof integrity. | ||
| 29 | **Cable Installation** | Cable conduit seals are intact; no exposed conductors or damaged insulation; no unauthorized or haphazard wiring. | ||
| 30 | **Static Discharge Device** | Human body static discharge device at the hazardous area entrance is intact and effectively grounded. | ||
| VI. Diesel Loading/Unloading, Transfer Pipelines, and Pump Area | ||||
| 31 | Transfer Pipelines | No deformation, corrosion, or leakage; supports are secure; medium flow direction is clearly marked. | ||
| 32 | Valves | Inlet/outlet valves and emergency shut-off valves are in good condition, operate smoothly, and are clearly marked; no internal or external leakage. | ||
| 33 | Emergency Shut-off Devices | Emergency shut-off valves at the tank base and loading/unloading stations function correctly; capable of remote and local shut-off. | ||
| 34 | Oil Transfer Pumps | No leakage from the pump body; seals are intact; explosion-proof motor operates without abnormal noise or overheating. | ||
| 35 | Loading/Unloading Platform | Spill alarm system functions correctly; loading arm seals are intact; grounding clamps are complete. | ||
| 36 | Hoses | Loading/unloading hoses show no signs of aging or cracking; undergo periodic pressure testing; not used beyond their service life. | ||
| VII. Safety Signage, Records, and Operational Management | ||||
| 37 | Safety Signage | Signage for "No Open Flames/Smoking," flammable liquids, explosion hazards, emergency evacuation, and medium identification is complete and clearly visible. | ||
| 38 | Operating Procedures | Standard operating procedures for tank loading/unloading, inspections, and emergency response are posted on-site. | ||
| 39 | Safety Records | Records for tank inspections, liquid level monitoring, lightning protection testing, anti-corrosion maintenance, hot work, and confined space operations are complete. | ||
| 40 | Special Operation Control | Strict adherence to work permit requirements for hot work, tank cleaning, and confined space operations within the zone; no unauthorized or uncertified work. | ||
| 41 | Personnel Protection | Personnel are equipped with anti-static workwear, safety footwear, and eye protection. | ||
| 42 | Emergency Records | Records of spill and fire emergency drills, as well as closed-loop records for hazard rectification, are complete. | ||
| VIII. Eco-friendly Anti-leakage Accessories | ||||
| 43 | Oil collection channels & oil-water separators | No blockages; cleaned regularly; floating oil recovered promptly. | ||
| 44 | Spill recovery | No long-term oil accumulation in green zones; minor spills can be diverted to collection pits. | ||
| 45 | Hazardous waste management | Used oil-absorbent pads and waste oil collected separately and stored according to standards; disposal records maintained. | ||
Latest News
Differences And Integrated Logic For Pressure Gauges, Pressure Transmitters, ...
Nov 04, 2026
Installed A Breakaway Coupling But Forgot To Remove The Safety Bolt? This Is ...
Nov 02, 2026
A Comprehensive Guide To Flowmeter Selection: From Media To Pipe Size—Everyth...
Oct 26, 2026
Required Flow Capacity For External Fire Exposure (Emergency Venting)
Oct 16, 2026
Contact Us
- High-tech Industrial Development Zone, Zhengzhou, Henan.
- sales@ottimafluid.com、peter@ottimafluid.com
-
+86-13503854331
-
Wechat: +86-13503854331 +86 13938423393
-
Whatsapp: +86-13503854331 +86 13938423393
On-Site Safety Inspection Checklist For Diesel Storage
Aug 20, 2026
You Might Also Like
Send Inquiry